The wattmeter reads iron losses in OC test and reads copper losses in SC test of a transformer. Justify.
1 Answer
written 3.5 years ago by |
Answer:
Open Circuit (OC) Test:
Fig. 1 OC Test
An ammeter, voltmeter and wattmeter are connected on this side. The ammeter indicates no-load current drawn by the transformer. As the no-load current is usually 3 to 5% of the full-load current, copper losses are negligible and the wattmeter indicates iron loss.
SHORT-CIRCUIT (SC) TEST