The following data are given for the space to be air conditioned: Outside air conditions = 40 C DBT and 50% RH,inside design conditions= 26 C DBT and 50% RH 50%, Apparatus Dew point = 10 C;

By pass factor of the cooling coil = 0.2

The return air from the room is mixed with the outside air before entry to the cooling coil in the ratio of 3:1 by mass If 20 m3/min of fresh air is supplied find:

i) Condition of air leaving the coil,

ii) Capacity of cooling coil in TR,

iii) Room sensible heat factor.

Mumbai University > Mechanical Engineering > Sem 8 > Refrigeration and air conditioning

Marks: 14M

Year: May 2016

1 Answer
0
186views

Locate point 'a' 40oC DBT and 50% RH and point 'b' 26oC and 50% RH and point 'd' 10oC and saturated condition on psychrometric chart. then locate the point 'c' in such a way

ac/bc=3/1

join c and d then locate point 'e' in such a way that

de/dc=0.2

i)condition …