1.Assumption:-
The 3-ø system considered here is a load, which is star connected.
The phase sequence is R→Y→B.
It is a balanced load.
The pf of each phase is logging.
2.Connection:-It is as shown in Fig (a)
3.Proof
Reading of wattmeter W1
W1=VABIRLcos(∠betweenVAB)&IRL=VLILcos(3θ0−∅ph)
Reading of wattmeter W2
W2=VABIYLcos(∠betweenVYB&IYL)=VLILcos(3θ0+∅ph)∴(w1+w2)=VLIL{cos(3θ0−∅ph)+cos(3θ0+∅ph)}={2cos(6002)cos(−2∅ph2)}VLIL=VLIL{2cos3θ0cos∅ph}=VLIL{7×√32,cos∅ph}=√3VLILcos∅=Total powervconsumede by the 3−∅load and hence the proof
Pharos Diagram